首页 | 本学科首页   官方微博 | 高级检索  
     

THE STUDY ON MEASURING TECHNIQUE OF PARTIAL DISCHARGE IN GAS INSULATED SWITCHGEAR USING ULTRA HIGH FREQUENCY METHOD WITH EXTERNAL SENSORS
引用本文:李忠 冯允平. THE STUDY ON MEASURING TECHNIQUE OF PARTIAL DISCHARGE IN GAS INSULATED SWITCHGEAR USING ULTRA HIGH FREQUENCY METHOD WITH EXTERNAL SENSORS[J]. 西安交通大学学报(英文版), 2005, 17(2): 101-104,109
作者姓名:李忠 冯允平
作者单位:School of Electrical Engineering,Xi'an Jiaotong University,Xi'an 710049,China,School of Electrical Engineering,Xi'an Jiaotong University,Xi'an 710049,China
基金项目:ThisstudywassupportedbytheScienceandTechniqueFoundationofNationalPowerNetworkCo.(No.SP1120010112)
摘    要:GISisusedwidelyallovertheworld,because theareaoccupiedbyaGISsubstationistypicallyon ly10-25%ofthatoftheequivalentairinsulated installation.Inordertoattainmorehighdegreeof reliabilityforGIS,thefailurescausedduringmanu facture,assemblinganderectionwillbeavo…

关 键 词:开关 接电装置 绝缘体 传感器 有限元分析 高压电 GIS 地理信息系统
文章编号:1671-8267(2005)02-0101-04

THE STUDY ON MEASURING TECHNIQUE OF PARTIAL DISCHARGE IN GAS INSULATED SWITCHGEAR USING ULTRA HIGH FREQUENCY METHOD WITH EXTERNAL SENSORS
Li Zhong,Feng Yunping. THE STUDY ON MEASURING TECHNIQUE OF PARTIAL DISCHARGE IN GAS INSULATED SWITCHGEAR USING ULTRA HIGH FREQUENCY METHOD WITH EXTERNAL SENSORS[J]. Academic Journal of Xi’an Jiaotong University, 2005, 17(2): 101-104,109
Authors:Li Zhong  Feng Yunping
Abstract:Objective In order to find early latent faults and prevent catastrophic failures, diagnosis of insulation condition by measuring technique of partial discharge(PD) in gas insulated switchgear (GIS) is applied in this paper, which is one of the most basic ways for diagnosis of insulation condition. Methods Ultra high frequency(UHF) PD detection method by using internal sensors has been proved efficient, because it may avoid the disturbance of corona, but the sensor installation of this method will be limited by the structure and operation condition of GIS. There are some of electromagnetic (E-M) waves leak from the place of insulation spacer, therefore, the external sensors UHF measuring PD technique is applied, which isn't limited by the operation condition of GIS. Results This paper analyzes propagated electromagnetic (E-M) waves of partial discharge pulse excited by using the finite-difference time-domain (FDTD) method. The signal collected at the outer point is more complex than that of the inner point, and the signals' amplitude of outer is about half of the inner, because it propagates through spacer and insulation slot. Set up UHF PD measuring system. The typical PD in 252kV GIS bus bar was measured using PD detection UHF technique with external sensors. Finally, compare the results of UHF measuring technique using external sensors with the results of FDTD method simulation and the traditional IEC60270 method detection. Conclusion The results of experiment shows that the UHF technique can realize the diagnosis of insulation condition, the results of FDTD method simulation and the result UHF method detection can demonstrate each other, which gives references to further researches and application for UHF PD measuring technique.
Keywords:gas insulated switchgear  partial discharge  ultra high frequency  finite-difference time-domain (FDTD) method  measurement  external sensor