首页 | 本学科首页   官方微博 | 高级检索  
     检索      

On-line detecting of transformer winding deformation based on parameter identification of leakage inductance
作者姓名:郝治国  张保会  李朋
作者单位:School of Electrical Engineering, Xi'an Jiaotong University, Xi'an 710049, China
摘    要:Transformers are required to demonstrate the ability to withstand short circuit currents. Over currents caused by short circuit can give rise to windings deformation. In this paper, a novel method is proposed to monitor the state of transformer windings, which is achieved through on-line detecting the leakage inductance of the windings. Specifically, the mathematical model is established for on-line identifying the leakage inductance of the windings by applying least square algorithm (LSA) to the equivalent circuit equations. The effect of measurement and model inaccuracy on the identification error is analyzed, and the corrected model is also given to decrease these adverse effect on the results. Finally, dynamic test is carried out to verify our method. The test results clearly show that our method is very accurate even under the fluctuation of load or power factor. Therefore, our method can be effectively used to on-line detect the windings deformation.

关 键 词:变压器  绕组变形  在线检测  漏电感  参数辨识
文章编号:1671-8267(2007)01-0024-05

On-line detecting of transformer winding deformation based on parameter identification of leakage inductance
Hao Zhiguo,Zhang Baohui,Li Peng.On-line detecting of transformer winding deformation based on parameter identification of leakage inductance[J].Academic Journal of Xi’an Jiaotong University,2007,19(1):24-28.
Authors:Hao Zhiguo  Zhang Baohui  Li Peng
Abstract:Transformers are required to demonstrate the ability to withstand short circuit currents.Over currents caused by short circuit can give rise to windings deformation.In this paper,a novel method is proposed to monitor the state of transformer windings,which is achieved through on-line detecting the leakage inductance of the windings.Specifically,the mathematical model is established for online identifying the leakage inductance of the windings by applying least square algorithm(LSA) to the equivalent circuit equations.The effect of measurement and model inaccuracy on the identification error is analyzed,and the corrected model is also given to decrease these adverse effect on the results.Finally,dynamic test is carried out to verify our method.The test results clearly show that our method is very accurate even under the fluctuation of load or power factor.Therefore,our method can be effectively used to on-line detect the windings deformation.
Keywords:Leakage inductance  parameter identification  windings deformation  on-line monitoring  least square  equivalent circuit equation
本文献已被 CNKI 维普 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号