首页 | 本学科首页   官方微博 | 高级检索  
     检索      

THE APPLICATION OF STATISTICAL PARAMETERS OF PHASE RESOLVED PD DISTRIBUTION TO AGING EXTENT ASSESSMENT OF LARGE GENERATOR INSULATION
作者姓名:谢恒堃  乐波  孙翔  宋建成
作者单位:State Key Laboratory of Electrical Insulation for Power Equipment,State Key Laboratory of Electrical Insulation for Power Equipment,State Key Laboratory of Electrical Insulation for Power Equipment,State Key Laboratory of Electrical Insulation for Power Equipment Xi'an Jiaotong University,Xi'an 710049,China,Xi'an Jiaotong University,Xi'an 710049,China,Xi'an Jiaotong University,Xi'an 710049,China,Xi'an Jiaotong University,Xi'an 710049,China
基金项目:ThisworkwassupportedbytheNationalNaturalScienceFoundationofChina (No .5 983 72 60 )
摘    要:Agingextentassessmentofgeneratorinsulationisofgreatsignificanceinplanninganeffectiveout ageandmaintenance .Inthelastdecade ,agingex tentassessmentoflargegeneratorinsulationwasasubjectresearchedintensively1-4] .Anumberofpa pershavebeenpublishedonthetechniquesofinsu lationconditiondiagnosisandagingextentassess mentofgeneratorinsulation .Nearlyalleffortsforinsulationdiagnosisandagingassessmenthavereliedonelectricalmeasurementsandmostattentionhasbeenpaidtoanalysisofcharacteristicsofpartialdis cha…


THE APPLICATION OF STATISTICAL PARAMETERS OF PHASE RESOLVED PD DISTRIBUTION TO AGING EXTENT ASSESSMENT OF LARGE GENERATOR INSULATION
Xie Hengkun,Yue Bo,Sun Xiang,Song Jiancheng State Key Laboratory of Electrical Insulation for Power Equipment,Xi'an Jiaotong University,Xi'an ,China..THE APPLICATION OF STATISTICAL PARAMETERS OF PHASE RESOLVED PD DISTRIBUTION TO AGING EXTENT ASSESSMENT OF LARGE GENERATOR INSULATION[J].Academic Journal of Xi’an Jiaotong University,2003,15(1).
Authors:Xie Hengkun  Yue Bo  Sun Xiang  Song Jiancheng State Key Laboratory of Electrical Insulation for Power Equipment  Xi'an Jiaotong University  Xi'an  China
Institution:State Key Laboratory of Electrical Insulation for Power Equipment, Xi'an Jiaotong University, Xi'an 710049, China
Abstract:Objective To investigate the characteristic parameters employed to describe the aging extent of stator insulation of large generator and study the aging laws. Methods Multi stress aging tests of model generator stator bar specimens were performed and PD measurements were conducted using digital PD detector with frequency range from 40?kHz to 400?kHz at different aging stage. Results From the test results of model specimens it was found that the skewness of phase resolved PD distribution might be taken as the characterization parameters for aging extent assessment of generator insulation. Furthermore, the measurement results of actual generator stator bars showed that the method based on statistical parameters of PD distributions are prospective for aging extent assessment and residual lifetime estimation of large generator insulation. Conclusion Statistical parameters of phase resolved PD distribution was proposed for aging extent assessment of large generator insulation.
Keywords:partial discharge  statistical parameters  stator insulation  multi  stress aging
本文献已被 CNKI 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号