津秦客运专线电缆贯通线电容电流补偿效果分析与测试
作者单位:;1.北京交通大学电气工程学院;2.中铁电气化局集团有限公司
摘    要:津秦客运专线10 kV供配电系统采用全电缆电力贯通线路,电缆线路中的电容电流会使贯通线末端电压升高并产生过量容性无功,通过分析、仿真和测试,对津秦客运专线的电容电流补偿方案进行验证,全电缆供配电系统系统中性点采用经过小电阻接地方式,采用沿线设置固定电抗器补偿和变、配电所内分组投切电抗器补偿相结合的容性电流补偿方法,再加上有载调压器的配合,可使供电电压水平和功率因数达到设计要求,获得良好供电指标。

关 键 词:客运专线  贯通线  电容电流  调压器  电抗器

Analysis and Testing on Compensation Effect of Capacitive Current of Cable Run-through Line for Tianjin-Qinhuangdao Railway Passenger-dedicated Line
Institution:,School of Electrical Engineering,Beijing Jiaotong University,China Railway Electrification Bureau Group Co.,Ltd.
Abstract:Electric run-through line with full cable was employed in the 10 kV power supply and distribution system of Tianjin-Qinhuangdao railway passenger-dedicated line.However,the capacitive current in the cable line may cause voltage rising at the end of the run-through line and may cause overmuch capacitive reactive power.For that reason,this paper verified the compensation scheme of capacitive current for Tianjin-Qinhuangdao railway passenger-dedicated line by means of analysis,simulation and testing.Meanwhile,the neutral point of the power supply and distribution system with full cable was earthed via the low resistance;the fixed electric reactor compensation along the railway was combined with the electric reactor compensation in the form of group switching within the substations and distribution substations,so as to do compensation of capacitive current;and all the measures were cooperated by on-load voltage regulators.It is concluded in this paper that by the use of solution measures above-mentioned,the power supply voltage level and power factors can meet design requirement,and a good power supply effect can be achieved.
Keywords:railway passenger-dedicated line  power run-through line  capacitive current  voltage regulator  electric reactor
本文献已被 CNKI 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号