首页 | 本学科首页   官方微博 | 高级检索  
     检索      

VFT PHASE VOLTAGE MEASUREMENT IN THREE-PHASE ENCLOSED GIS
作者姓名:邹建华  岳子丁  李洋
作者单位:Systems Engineering Institute,Xi'an Jiaotong University,Systems Engineering Institute,Xi'an Jiaotong University,Systems Engineering Institute,Xi'an Jiaotong University Xi'an 710049,China,Xi'an 710049,China,Xi'an 710049,China
摘    要:Gasinsulatedsubstation (GIS)havebeenusedinawiderangeofvoltagelevelfrom 12 3kVto765kVorabove .Asvoltagelevelsexceed 30 0kV ,failurescausedbyelectromagnetictransientphenom enabegintoappear .Theseelectromagnetictran sientsarecausedbydisconnectswitchingintheGIS .This…


VFT PHASE VOLTAGE MEASUREMENT IN THREE-PHASE ENCLOSED GIS
Zou Jianhua,Yue Ziding,Li YangSystems Engineering Institute,Xi'an Jiaotong University,Xi'an ,China..VFT PHASE VOLTAGE MEASUREMENT IN THREE-PHASE ENCLOSED GIS[J].Academic Journal of Xi’an Jiaotong University,2002,14(2):101-108.
Authors:Zou Jianhua  Yue Ziding  Li YangSystems Engineering Institute  Xi'an Jiaotong University  Xi'an  China
Institution:Systems Engineering Institute, Xi'an Jiaotong University, Xi'an 710049, China.
Abstract:The measuring of VFT phase voltage in three-phase enclosed GIS is more complex and difficult than in single-phase ones. There are 3 capacitive sensors in the measuring system, the outputs of which are with a linear relation to the three phase voltages. This linear relation is presented with a factorial matrix. Because each capacitive sensor is coupled with the electric field of three phases (A, B, and C), the electric coupling coefficients are introduced. In order to determine the matrix of electric coupling coefficients, the numerical calculation method can be used. From the discussion on two types of three-phase enclosed GIS bus, i.e. standard arrangement and biased arrangement, the dominant electric coupling coefficients are named, which can be simply and approximately calculated by an analytic expression. Finally, as an example, the waveforms of VFT phase voltage generated on a three-phase enclosed GIS bus model are displayed. When a capacitive sensor is located at the 'shortest point' of phase A (or B, or C), the VFT phase voltage V A (or V B, or V C) can almost be measured by that capacitive sensor alone.
Keywords:gas insulated substation(GIS)  very fast transients(VFT)  voltage measurement  electric field  analytic expression  measurement apparatus  VFT phase voltage wave
本文献已被 CNKI 维普 万方数据 等数据库收录!