首页 | 本学科首页   官方微博 | 高级检索  
     检索      


Influence of the type of the pulverized coal concentrator on the operation of a tangential fired boiler with horizontal bias combustion
Authors:Xiaoyan Guan  Xinli Zou  Shaozeng Sun
Institution:GUAN Xiaoyan;ZOU Xinli;SUN Shaozeng;College of Urban Construction and Safely Engineering,Shanghai Institute of Technology;Research Institute of Combustion Engineering,Harbin Institute of Technology;
Abstract:In this paper, the problems of combustion instability and high-temperature corrosion of pulverized coal fired boiler are investigated by numerical simulation and analysis of the momentum moment. Elbow and twisting plate type of burners are used in the boiler, and the reverse moment of momentum is formed at the outlet of the fuel-rich side of the burner. The momentum moment in the boiler is opposite to the designed tangential circle, and the tangential circle in the boiler is reversed rotation. The reverse moment of momentum at the burner outlet can be eliminated by using louver horizontal bias pulverized coal burner, while the problems of combustion instability and high-temperature corrosion of the boiler are solved, and the combustion efficiency is improved. Accordingly, economic benefit is obviously got.
Keywords:
本文献已被 CNKI SpringerLink 等数据库收录!