首页 | 本学科首页   官方微博 | 高级检索  
     检索      

单芯电力电缆接地施工技术
引用本文:王军,傅永德,郭旭振.单芯电力电缆接地施工技术[J].铁道建筑技术,2011(1):56-58.
作者姓名:王军  傅永德  郭旭振
作者单位:中铁十二局集团电气化工程有限公司,太原,030024
摘    要:单芯电力电缆在运行中金属屏蔽和铠装层两端接地,会在金属屏蔽和铠装层中形成环流,引起电缆发热,影响电缆载流量;如果一端接地,则另一端就会出现感应电压,危及人身和设备安全。针对这两种情况,介绍了在安哥拉市政电力工程实际施工中采取的方法和措施。

关 键 词:电力电缆  金属护套  接地  监测装置

Construction Technologies of Single Core Power Cable Grounding
Wang Jun,Fu Yongde,Guo Xuzhen.Construction Technologies of Single Core Power Cable Grounding[J].Railway Construction Technology,2011(1):56-58.
Authors:Wang Jun  Fu Yongde  Guo Xuzhen
Institution:Wang Jun,Fu Yongde,Guo Xuzhen(China Railway 12~(th) Bureau Group Co.Ltd.,Taiyuan 030024,China)
Abstract:When both ends of the metal sheath and armoured level are grounded,circulation will occur there during the operation of the single core power cable,which causes heat in cables and affects their current carrying capacity.On the other hand,if only one end is connected,inductive voltage will be created on the other end,endangering people and equipment.This paper,in accordance with the two different conditions,introduces our actual methods and measures adopted in Angola municipal power engineering.
Keywords:power cable  metal sheath  grounding  monitor device  
本文献已被 CNKI 维普 万方数据 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号