首页 | 本学科首页   官方微博 | 高级检索  
     


Air Cored Rogowski Coil for Measurement of Partial Discharges
Authors:SUN Zhen-quan  ZHAO Xue-feng  LI Ji-sheng  LI Yan-ming
Affiliation:School of Electrical Engineering,Xi'an Jiaotong University,Xi'an 710049,China;}
Abstract:A Rogowski coil was designed to measure partial discharge (PD) signal with low currents and high frequency. The possibilities of obtaining better measurements of PDs were explored by changing the inductance, mutual inductance, resistance, and capacitance of the coil. The designed Rogowski coil was calibrated under square wave voltage and arbitrary sine wave voltage. Then, according to the parameters of the Rogowski coil, the effect of changing some of these variables was simulated using a bode plot. Compari...
Keywords:Air cored Rogowski coil  Partial discharge  Measurement  Calibration  
本文献已被 CNKI 维普 万方数据 等数据库收录!