首页 | 本学科首页   官方微博 | 高级检索  
     检索      


Experimental study of the airside performance for interrupted fin-and-tube heat exchanger with hydrophilic coating under dehumidifying conditions
Authors:Xiao-kui Ma  Guo-liang Ding  Yuan-ming Zhang
Institution:(1) Institute of Refrigeration and Cryogenics, Shanghai Jiaotong University, Shanghai, 200240, China
Abstract:The airside heat transfer and friction characteristics of seven interrupted fin-and-tube heat exchangers with hydrophilic coating under dehumidifying conditions are experimented. The effects of number of tube rows, fin pitch and inlet relative humidity on airside performance are analyzed. The test results show that the influence of fin pitch on the friction characteristic under dehumidifying conditions is similar to that under dry surface, and the friction factors decrease slightly with the increase of number of tube rows. The heat transfer performance decreases as fin pitch and number of tube rows increases. The heat transfer performance and the friction characteristic are independent of inlet relative humidity. Based on the test results, heat transfer and friction correlations in terms of the Colburn j factor and Fanning f factor, are proposed to describe the airside performance of the interrupted fin geometry with hydrophilic coating under dehumidifying conditions. The correlation of the Colburn j factor gives a mean deviation of 9.7%, while the correlation of the Fanning f factor shows a mean deviation of 7.3%.
Keywords:interrupted fin  dehumidifying conditions  hydrophilic coating  heat transfer  friction
本文献已被 维普 万方数据 SpringerLink 等数据库收录!
设为首页 | 免责声明 | 关于勤云 | 加入收藏

Copyright©北京勤云科技发展有限公司  京ICP备09084417号